Power Relays
G7L General Purpose Relay
A High-capacity, High-dielectricstrength
Relay Compatible with
Momentary Voltage Drops
- No contact chattering for momentary vol]tage
drops up to 50% of rated voltage.
- Wide-range AC-activated coil that handles
100 to 120 or 200 to 240 VAC at either 50 or
60 Hz.
- Miniature hinge for maximum switching power,
particularly for inductive loads.
- Flame-resistance materials (UL94V-0-
qualifying) used for all insulation material.
- Quick-connect, screw, and PCB terminals,
and DIN track mounting available.
 |
|
|
|
Updated March 23, 2009
|
This web page provides an excerpt from a datasheet. Refer to Datasheetand other applicable documents for more information.
| Mounting Type |
Contact form |
Quick-connect
terminals |
Screw terminals
terminals |
PCB terminals |
| E-bracket |
SPST-NO |
G7L-1A-T |
G7L-1A-B |
- |
| DPST-NO |
G7L-2A-T |
G7L-2A-B |
- |
E-bracket (with
test button) |
SPST-NO |
G7L-1A-TJ |
G7L-1A-BJ |
- |
| DPST-NO |
G7L-2A-TJ |
G7L-2A-BJ |
- |
| Upper bracket |
SPST-NO |
G7L-1A-TUB |
G7L-1A-BUB |
- |
| DPST-NO |
G7L-2A-TUB |
G7L-2A-BUB |
- |
Upper bracket
(with test button) |
SPST-NO |
G7L-1A-TUBJ |
G7L-1A-BUBJ |
- |
| DPST-NO |
G7L-2A-TUBJ |
G7L-2A-BUBJ |
- |
| PCB mounting |
SPST-NO |
- |
- |
G7L-1A-P |
| DPST-NO |
- |
- |
G7L-2A-P |
| Note: |
1. |
When ordering, add the rated coil voltage to the model number. |
| |
. |
Example: G7L-1A-T |
 |
Accessories (Order Separately)
| Terminals |
Contact form |
Model |
P99-07
E-brackets |
P7LF-D DIN
Track Mounting
Adapter |
P7LF-06
Front Connecting
Socket |
Quick-connect
terminals |
SPST-NO
| G7L-1A-T |
Yes |
Yes |
Yes |
| G7L-1A-TJ |
Yes |
Yes |
Yes |
| DPST-NO
| G7L-2A-T |
Yes |
Yes |
Yes |
| G7L-2A-TJ |
Yes |
Yes |
Yes |
| Screw terminals |
SPST-NO
| G7L-1A-B |
Yes |
Yes |
No |
| G7L-1A-BJ |
Yes |
Yes |
No |
| DPST-NO
| G7L-2A-B |
Yes |
Yes |
No |
| G7L-2A-BJ |
Yes |
Yes |
No |
| Applicable Relay |
Name |
Model |
| G7L-1A-T/G7L-1A-TJ/G7L-1A-B/G7L-1A-BJ
G7L-2A-T/G7L-2A-TJ/G7L-2A-B/G7L-2A-BJ |
E-bracket |
R99-07 |
| Adapter |
P7LF-D |
| G7L-1A-T/G7L-1A-TJ/G7L-2A-T/G7L-2A-TJ |
Front-connecting Socket |
P7LF-06 |
G7L-1A-B/G7L-1A-BJ/G7L-1A-BUB/G7L-1A-BUBJ
G7L-2A-B/G7L-2A-BJ/G7L-2A-BUB/G7L-2A-BUBJ |
Cover |
P7LF-C |
Coil Ratings
| Rated Voltage |
Rated
current |
Coil
resistance |
Must operate
voltage |
Must release
voltage |
Max. voltage |
Power
consumption
(approx.) |
| AC (~) |
12 V |
142 mA |
- |
75% max. of
rated voltage |
15% min. of
rated voltage |
110% of
rated voltage |
1.7 to 2.5 VA
(60 Hz) |
| 24 V |
71 mA |
- |
| 50 V |
34 mA |
- |
| 100 to 120 V |
7.0 to
20.4 mA |
- |
75 V |
18 V |
132 V |
| 200 to 240 V |
8.5 to
10.2 mA |
- |
150 V |
36 V |
264 V |
| DC (=) |
6 V |
317 mA |
18.9 Ω |
75% max. of
rated voltage |
15% min. of
rated voltage |
110% of
rated voltage |
1.9 W |
| 12 V |
158 mA |
75Ω |
| 24 V |
79 mA |
303Ω |
| 48 V |
40 mA |
1220Ω |
| 100 V |
19 mA |
5260 |
| Note: |
1. |
The rated current and coil resistance
are measured at a coil temperature of 23ºC with tolerances
of +15%/-20% for AC rated current and ±15% for DC coil
resistance. |
|
2. |
Performance characteristic data are measured
at a coil temperature of 23ºC. |
| |
3. |
~ indicates AC and = indicates DC (IEC417
publications). |
Contact Ratings
| Model |
G7L-1A-T /G7L-1A-B |
G7L-2A-T /G7L-2A-B |
G7L-1A-P/G7L-2A-P |
Resistive load
(cosφ = 1) |
Inductive load
(cosφ = 0.4) |
Resistive load
(cosφ = 1) |
Inductive load
(cosφ = 0.4) |
Resistive load
(cosφ = 1) |
Inductive load
(cosφ = 0.4) |
| Rated Load |
30 A, 220 VAC
(~) |
25 A, 220 VAC
(~) |
25 A, 220 VAC
(~) |
25 A, 220 VAC
(~) |
| Carry Current |
30 A |
25 A |
20 A |
Max. switching
voltage |
250 VAC (~) |
250 VAC (~) |
250 VAC (~) |
Max. switching
current |
30 A |
25 A |
20 A |
Max. switching
power |
6,600 VAC (~) |
5,500 VAC (~) |
5,500 VAC (~) |
4,400 VAC (~) |
Failure rate*
(reference value) |
100 mA, 5 VDC (~) |
100 mA, 5 VDC (~) |
100 mA, 5 VDC (~) |
| Note: |
P level: λ60 =
0.1 x 10-6/operation |
Characteristics
| Contact resistance |
50 mΩ max. |
| Operate time |
30 ms max. |
| Release time |
30 ms max. |
| Max. operating frequency |
Mechanical: 1,800 operations/hr
Electrical: 1,800 operations/hr
(under rated load) |
| Insulation resistance |
1,000
MΩ min. (at 500 VDC) |
| Dielectric strength |
4,000 VAC min., 50/60 Hz for 1 min between
coil and contacts
2,000 VAC, 50/60 Hz for 1 min between
contacts of same polarity
2,000 VAC, 50/60 Hz for 1 min between
contacts of different polarity (DPST-NO model) |
| Impulse withstand voltage |
10,000 V between coil and contact (with 1.2 x 50 μs
impulse wave) |
| Vibration resistance |
| Destruction: |
10 to 55 to, 0.75 mm single amplitude (1.5 mm double
amplitude) |
| Malfunction: |
10 to 55 to, 0.75 mm single amplitude (1.5 mm double
amplitude) |
|
| Shock resistance |
| Destruction: |
1,000 m/s2 |
| Malfunction: |
100 m/s2 |
|
| Endurance |
| Mechanical: |
1,000,000 operations min. (at 1,800 operations/hr) |
| Electrical: |
100,000 operations min. (at 1,800 operations/hr
under rated load) |
|
| Ambient temperature |
Operating: -25ºC to 60ºC (with
no icing) |
| Ambient humidity |
Operating: 5% to 85% |
| Weight |
Quick-connect terminal models: approx.
90 g
PCB terminal models: approx. 100
g
Screw terminal models: approx.
120 g |
| Note: |
The values given above are initial values |
|
Relays
Product Lineup
Support