Power Relays

Search by product list
G2RG PCB Relay
Power Relay with 1.5-mm Contact Gap
  • Clearance between contact terminals of the same polarity: 1.5 mm min.
  • Meets the requirements of European UPS standards.
    Note:UPS: Uninterruptible power systems.
  • Conforms to VDE0435 (VDE approval: C250 insulation grade), UL508, CSA22.2.
  • Meets VDE0700 requirements for household products according to VDE0110.
  • Cadmium-free contacts ensuring environmentfriendly use.
  • Tracking resistance: CTI > 250 V.
G2RG
JPN
OrderingInformationRatings / CharacteristicsDimensions
Contact form
Rated coil voltage
Model number
DPST-NO 12 VDC
24 VDC
G2RG-2A4
OrderingInformationRatings / CharacteristicsDimensions
Coil Ratings
Rated voltage
Rated current
Coil resistance
Must-operate
voltage
Must-release
voltage
Maximum
allowable
voltage
Power
consumption
12 VDC 66.6 mA 180 Ω 80% max. 10% min. 140%
(at 23ºC)
Approx. 800 mW
24 VDC 33.3 mA 720 Ω
Note:1. The rated current and coil resistance are for a coil temperature of 23ºC and have a tolerance of ±10%.
2. The operating characteristics given in the above table are for a coil temperature of 23ºC.
3. The maximum allowable voltage is the maximum possible value of the voltage that can be applied to the relay coil.

Contact Ratings
Load Resistive load
Contact mechanism Single
Contact material Ag alloy
Rated load 250 VAC, 8 A
Rated carry current 8A
Maximum switching voltage 380 VAC, 125 VDC
Maximum switching current 8 A
Failure rate (P level, reference value)
(See note.)
5 VDC, 10mA
Note:This value is for a switching frequency of 120 operations/min.

Characteristics
Contact resistance
(See note 1.)
100 mΩ max.
Operate time 15 ms max.
Release time 5 ms max.
Maximum switching frequency Mechanical 18,000 operations/hr
Electrical 1,800 operations/hr (under rated load)
Insulation resistance
(See note 2.)
1,000MΩ min. (at 500 VDC)
Dielectric strength 5,000 VAC, 50/60 Hz for 1 min between coil and contacts
3,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts of the same polarity
Impulse withstand voltage 10 kV (1.2 × 50 μs)
Vibration resistance Destruction 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance Destruction 1,000 m/s2
Malfunction 200m/s2 when energized
Endurance Mechanical 1,000,000 operations min. (at 18,000 operations/hr)
Electrical 10,000 operations min. (at 1,800 operations/hr under rated load)
Ambient operating temperature -40 to 70 ºC (with no icing or condensation)
Ambient operating humidity 55% to 85%
Weight Approx. 17.2 g
Note:1. The above values are initial values (at an ambient temperature of 23 ºC).
2. Measurement conditions: 5 VDC, 1 A, voltage-drop method.
3. Measurement conditions: Measured with a 500-VDC megohmmeter at the same places as the dielectric strength.
OrderingInformationRatings / CharacteristicsDimensions
G2RG-2A4
G2RG-2A4:Dimensions1
*Figures in parentheses indicate average values.
 
PCB Mounting Holes(BOTTOM VIEW)
G2RG-2A4:Dimensions2
Terminal Arrangement /
Internal Connections

(BOTTOM VIEW)
G2RG-2A4:Dimensions3
(The coil has no polarity.)