A Power Relay for a Variety of Purposes with Various Models
Updated Aug. 31, 2012
| Model | 2D CAD | 3D CAD | ||
|---|---|---|---|---|
| G2R-2 | G2R-2.DXF [93KB] | G2R-2.DWG [57KB] | Display | Download |
| G2R-2-Z | G2R-2-Z.DXF [93KB] | G2R-2-Z.DWG [57KB] | Display | Download |
| G2R-2-H | G2R-2-H.DXF [93KB] | G2R-2-H.DWG [57KB] | Display | Download |
| G2R-2A | G2R-2A.DXF [93KB] | G2R-2A.DWG [57KB] | Display | Download |
| G2R-2A-H | G2R-2A-H.DXF [93KB] | G2R-2A-H.DWG [57KB] | Display | Download |
| G2R-2A-Z | G2R-2A-Z.DXF [93KB] | G2R-2A-Z.DWG [57KB] | Display | Download |
| G2R-24 | G2R-24.DXF [93KB] | G2R-24.DWG [57KB] | Display | Download |
| G2R-24-Z | G2R-24-Z.DXF [93KB] | G2R-24-Z.DWG [57KB] | Display | Download |
| G2R-24-U | G2R-24-U.DXF [93KB] | G2R-24-U.DWG [57KB] | Display | Download |
| G2R-2A4 | G2R-2A4.DXF [93KB] | G2R-2A4.DWG [57KB] | Display | Download |
| G2R-2A4-Z | G2R-2A4-Z.DXF [93KB] | G2R-2A4-Z.DWG [57KB] | Display | Download |
| G2R-2A4-U | G2R-2A4-U.DXF [93KB] | G2R-2A4-U.DWG [57KB] | Display | Download |
This web page provides an excerpt from a datasheet. Refer to
Datasheet and other applicable documents for more information.
| Classification | Enclosure ratings | Contact form | Model | Rated coil voltage |
|---|---|---|---|---|
| General-purpose | Flux protection | NO | G2R-2A | 12, 24, 100/(110) VAC |
| 200/(220) VAC | ||||
| 5, 6, 12, 24, 48 VDC | ||||
| 100 VDC | ||||
| NO/NC | G2R-2 | 12, 24, 100/(110) VAC | ||
| 200/(220) VAC | ||||
| 5, 6, 12, 24, 48 VDC | ||||
| 100 VDC | ||||
| Fully sealed | NO | G2R-2A4 | 12, 24, 100/(110) VAC | |
| 200/(220) VAC | ||||
| 5, 6, 12, 24, 48 VDC | ||||
| 100 VDC | ||||
| NO/NC | G2R-24 | 12, 24, 100/(110) VAC | ||
| 200/(220) VAC | ||||
| 5, 6, 12, 24, 48 VDC | ||||
| 100 VDC | ||||
| High-sensitivity | Flux protection | NO | G2R-2A-H | 5, 6, 12, 24, 48 VDC |
| NO/NC | G2R-2-H | 5, 6, 12, 24, 48 VDC | ||
| Double-winding latching |
NO | G2RK-2A | 5, 6, 12, 24 VDC | |
| NO/NC | G2RK-2 | 5, 6, 12, 24 VDC |
| Note: | When ordering, add the rated coil voltage to the model number. |
| Example: G2R-1A |
| Classification | Enclosure rating | Contact form | Number of poles :1-pole | |
|---|---|---|---|---|
| Model | Rated coil voltage | |||
| General-purpose | Flux protection | NO | G2R-2A-Z | 5, 6, 12, 24, 48 VDC |
| 100 VDC | ||||
| NO/NC | G2R-2-Z | 12, 24, 48 VDC | ||
| 100 VDC | ||||
| Fully sealed | NO | G2R-2A4-Z | 24, 48 VDC | |
| 100 VDC | ||||
| NO/NC | G2R-24-Z | 5, 12, 24 VDC | ||
| 100 VDC | ||||
| Classification | Enclosure rating | Contact form | Number of poles :1-pole | |
|---|---|---|---|---|
| Model | Rated coil voltage | |||
| General-purpose | Fully sealed | NO | G2R-2A4-U | 100/(110) VAC |
| − | ||||
| 5, 12, 24 VDC | ||||
| NO/NC | G2R-24-U | 12, 24, 100/(110) VAC 200/(220) VAC |
||
| 5, 12, 24, 48 VDC | ||||
| 100 VDC | ||||
|
Item
Rated voltage
Classification |
Rated current (mA) | Coil resistance (Ω) |
Must operate voltage (V) |
Must release voltage (V) |
Max. voltage (V) |
Power consumption (VA, W) |
||
|---|---|---|---|---|---|---|---|---|
| 50 Hz | 60 Hz | % of rated voltage | ||||||
| •General-purpose •Quick-connect •Fully sealed •High-capacity |
12 VAC | 93 | 75 | 65 | 80% max. | 30% min. | 140% (at 23°C) |
Approx. 0.9 (60 Hz) |
| 24 VAC | 46.5 | 37.5 | 260 | |||||
| 100/(110) VAC | 11 | 9/(10.6) | 4,600 | |||||
| 200/(220) VAC | 5.5 | 4.5/(5.3) | 20,200 | |||||
|
•General-purpose •High-capacity •Bifurcated contact •Quick-connect •Fully sealed |
5 VDC | 106 | 47 | 70% max. | 15% min. | 170% (at 23°C) |
Approx. 0.53 | |
| 6 VDC | 88.2 | 68 | ||||||
| 12 VDC | 43.6 | 275 | ||||||
| 24 VDC | 21.8 | 1,100 | ||||||
| 48 VDC | 11.5 | 4,170 | ||||||
| 100 VDC | 5.3 | 18,860 | ||||||
| •High-sensitivity | 5 VDC | 71.4 | 70 | 70% max. | 15% min. | 170% (at 23°C) |
Approx. 0.36 | |
| 6 VDC | 60 | 100 | ||||||
| 12 VDC | 30 | 400 | ||||||
| 24 VDC | 15 | 1,600 | ||||||
| 48 VDC | 7.5 | 6,400 | ||||||
| Note: | 1. | The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of+15%/-20% (AC rated current) or ±10% (DC coil resistance). |
| 2. | AC coil resistances shown above are only reference values. | |
| 3. | The operating characteristics are measured at a coil temperature of 23°C. | |
| 4. | The “Max. voltage” is the maximum voltage that can be applied to the relay coil. |
Item
Rated voltage |
Set Coil | Reset coil | Must operate voltage (V) |
Must release voltage (V) |
Max. voltage (V) |
Power consumption (VA, W) |
|||
|---|---|---|---|---|---|---|---|---|---|
| Rated current (mA) |
Coil resistance (Ω) |
Rated current (mA) |
Coil resistance (Ω) |
% of rated voltage | Set Coil (mW) |
Reset coil (mW) |
|||
| 5 VDC | 167 | 30 | 119 | 42 | 70% max. | 70% max. | 140% (at 23°C) |
Approx. 850 |
Approx. 600 |
| 6 VDC | 138 | 43.5 | 100 | 60 | |||||
| 12 VDC | 70.6 | 170 | 50 | 240 | |||||
| 24 VDC | 34.6 | 694 | 25 | 960 | |||||
| Note: | 1. | The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of+15%/-20% (AC rated current) or ±10% (DC coil resistance). |
| 2. | The operating characteristics are measured at a coil temperature of 23°C. | |
| 3. | The “Max. voltage” is the maximum voltage that can be applied to the relay coil. |
|
Classification
Number of poles
Load
Item |
General-purpose Quick-connect Terminal (1single-pole type) |
|||
|---|---|---|---|---|
| 1-pole | 2-pole | |||
| Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Single | |||
| Contact material | Ag-alloy (Cd free) | |||
| Rated load | 10 A at 250 VAC 10 A at 30 VDC |
7.5 A at 250 VAC 5 A at 30 VDC |
5 A at 250 VAC 5 A at 30 VDC |
2 A at 250 VAC 3 A at 30 VDC |
| Rated carry current | 10 A | 5 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | |||
| Max. switching current | 10 A | 5 A | ||
| Failure rate (P level) (reference value) * |
100 mA at 5 VDC | 10 mA at 5 VDC | ||
| Classification
Number of poles
Load
Item |
High-capacity | Bifurcated contact | ||
|---|---|---|---|---|
| 1-pole | 2-pole | |||
| Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Single | Bifurcated | ||
| Contact material | Ag-alloy (Cd free) | |||
| Rated load | 16 A at 250 VAC 16 A at 30 VDC |
8 A at 250 VAC 8 A at 30 VDC |
5 A at 250 VAC 5 A at 30 VDC |
2 A at 250 VAC 3 A at 30 VDC |
| Rated carry current | 16 A | 5 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | |||
| Max. switching current | 16 A | 5 A | ||
| Failure rate (P level) (reference value) * |
100 mA at 5 VDC | 10 mA at 5 VDC | ||
| Classification
Number of poles
Load
Item |
High-sensitivity | |||
|---|---|---|---|---|
| 1-pole | 2-pole | |||
| Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
Resistive load |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Single | |||
| Contact material | Ag-alloy (Cd free) | |||
| Rated load | 5 A at 250 VAC 5 A at 30 VDC |
2 A at 250 VAC 3 A at 30 VDC |
3 A at 250 VAC 3 A at 30 VDC |
1 A at 250 VAC 1.5 A at 30 VDC |
| Rated carry current | 5 A | 3 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | |||
| Max. switching current | 5 A | 3 A | ||
| Failure rate (P level) (reference value) * |
100 mA at 5 VDC | 10 mA at 5 VDC | ||
| Classification
Number of poles
Load
Item |
General-purpose (Single contact) | |||
|---|---|---|---|---|
| 1-pole | 2-pole | |||
| Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Single | |||
| Contact material | Ag-alloy (Cd free) | |||
| Rated load | 8 A at 250 VAC 8 A at 30 VDC |
6 A at 250 VAC 4 A at 30 VDC |
4 A at 250 VAC 4 A at 30 VDC |
1.5 A at 250 VAC 2.5 A at 30 VDC |
| Rated carry current | 8 A | 4 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | 380 VAC, 125 VDC | ||
| Max. switching current | 8 A | 4 A | ||
| Failure rate (P level) (reference value) * |
100 mA at 5 VDC | 10 mA at 5 VDC | ||
| Classification
Number of poles
Load
Item |
Bifurcated contact | |
|---|---|---|
| 1-pole | ||
| Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Bifurcated | |
| Contact material | Ag-alloy (Cd free) | |
| Rated load | 5 A at 250 VAC 5 A at 30 VDC |
2 A at 250 VAC 3 A at 30 VDC |
| Rated carry current | 5 A | |
| Max. switching voltage | 380 VAC, 125 VDC | |
| Max. switching current | 5 A | |
| Failure rate (P level) (reference value) * |
1 mA at 5 VDC | |
Classification
Load
Item |
1-pole | 2-pole | ||
|---|---|---|---|---|
| Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4; L/R = 7 ms) |
|
| Contact type | Single | |||
| Contact material | Ag-alloy (Cd free) | |||
| Rated load | 5 A at 250 VAC 5 A at 30 VDC |
3.5 A at 250 VAC 2.5 A at 30 VDC |
3 A at 250 VAC 3 A at 30 VDC |
1.5 A at 250 VAC 2 A at 30 VDC |
| Rated carry current | 5 A | 3 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | 380 VAC, 125 VDC | ||
| Max. switching current | 5 A | 3 A | ||
| Failure rate (P level) (reference value) * |
100 mA at 5 VDC | 10 mA at 5 VDC | ||
|
Number of poles
Item |
1-pole | 2-pole | |
|---|---|---|---|
| Contact resistance *1 | 30 mΩmax. *2 | 50 mΩ max. | |
| Operate time *3 | 15 ms max. | ||
| Release time *3 | AC: 10 ms max.; DC: 5 ms max. | ||
| Max. operating frequency |
Mechanical | 18,000 operations/hr | |
| Electrical | 1,800 operations/hr | ||
| Insulation resistance *4 | 1,000 MΩ min. | ||
| Dielectric strength |
Between coil and contacts |
5,000 VAC, 50/60 Hz for 1 min | |
| Between contacts of different polarity |
3,000 VAC, -50/60 Hz for 1 min |
||
| Between contacts of the same polarity |
1,000 VAC, 50/60 Hz for 1 min | ||
| Vibration resistance |
Destruction | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
|
| Malfunction | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
||
| Shock resistance |
Destruction | 1,000 m/s2 | |
| Malfunction | 200 m/s2 when energized; 100m/s2 when no energized |
||
| Durability | Mechanical | AC coil: 10,000,000 operations min.; DC coil: 20,000,000 operations min. (at 18,000 operations/hr) |
|
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) |
||
| Ambient operating temperature | -40°C to 70ºC (with no icing) | ||
| Ambient operating humidity | 5% to 85% | ||
| Weight | Approx. 17 g (Approx. 20 g *5) | ||
| * | 1. | Measurement conditions: 5 VDC, 1 A, voltage-drop method. |
| * | 2. | High-capacity type: 100 mΩ max. |
| * | 3. | Measurement conditions: Rated operating voltage applied, not including contact bounce. |
| * | 4. | Measurement conditions: The insulation resistance was measured with a 500 VDC megohmmeter at the same locations as the dielectric strength was measured. |
| * | 5. | Value for quick-connect terminals. |
| Number of poles
Item |
1-pole | 2-pole | |
|---|---|---|---|
| Contact resistance *1 | 30 mΩmax. *2 | 50 mΩ max. | |
| Set | Time *2 | 20 ms max. | |
| Min. set pulse width | 30 ms | ||
| Reset | Time *2 | 20 ms max. | |
| Min. reset pulse width |
30 ms | ||
| Max. operating frequency |
Mechanical | 18,000 operations/hr | |
| Electrical | 1,800 operations/hr | ||
| Insulation resistance *3 | 1,000 MΩ min.(at 500 VDC) | ||
| Dielectric strength |
Between coil and contacts |
5,000 VAC, 50/60 Hz for 1 min | |
| Between contacts of different polarity |
3,000 VAC, -50/60 Hz for 1 min |
||
| Between contacts of the same polarity |
1,000 VAC, 50/60 Hz for 1 min | ||
| Vibration resistance |
Destruction | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
|
| Malfunction | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
||
| Shock resistance |
Destruction | 1,000 m/s2 | |
| Malfunction | Set: 500m/s2 Armature OFF Reset: 200m/s2 Contact OFF |
||
| Durability | Mechanical | 100,000 operations min. (at 1,800 operations/hr under rated load) |
|
| Electrical | 100,000 operations min. (at 1,800 operations/hr under rated load) |
||
| Ambient operating temperature | -40°C to 70ºC (with no icing or condensation) | ||
| Ambient operating humidity | 5% to 85% | ||
| Weight | Approx. 17 g | ||
| * | 1. | Measurement conditions: 5 VDC, 1 A, voltage-drop method. |
| * | 2. | Measurement conditions: Rated operating voltage applied, not including contact bounce. |
| * | 3. | Measurement conditions: The insulation resistance was measured with a 500 VDC megohmmeter at the same locations as the dielectric strength was measured. |
Double-winding Latching Relays with PCB Terminals DPDT Relays G2RK-2 ![]() |
|||
|
|||
|
DPST-NO Relays G2RK-2A ![]() |
|||
|
|||
|
Relays with PCB Terminals DPDT Relays G2R-2, G2R-2-H ![]() |
|||
|
|||
| DPST-NO Relays G2R-2A, G2R-2A-H ![]() |
|||
|
|||
| DPDT Relays G2R-24 ![]() |
|||
|
|||
| DPST-NO Relays G2R-2A4 ![]() |
|||
|
|||
Precautions
When mounting a number of relays on a PCB, be sure to provide a minimum mounting space of 5 mm between the two juxtaposed relays as shown below.
The above minimum mounting space is necessary due to mutual thermal interference generated by the relays. This restriction may be ignored, however, depending on the operating conditions of the relays. Consult OMRON for details.
There is no restriction on the mounting direction of each relay on the PCB.
When using this circuit, confirm the set and reset states and then take into account the circuit constant.