DC Power Relays G9E□ Series
G9EC-1 DC Power Relays(200-A Models)
DC Power Relays Capable of Interrupting High-voltage, High-current Loads
A compact relay (98 × 44 × 86.7 mm (L × W × H)) capable of switching 400-V 200-A DC loads. (Capable of interrupting 1,000 A at 400 VDC max.)
- The switching section and driving section are gas-injected and hermetically sealed, allowing these compact relays to interrupt high-capacity loads. The sealed construction also requires no arc space, saves space, and helps ensure safe applications.
- Downsizing and optimum design allow no restrictions on the mounting direction.
- Terminal Cover is also available for industrial applications.
- UL/CSA standard UL508 approved.
 |
|
|
|
Updated March 23, 2009
|
This web page provides an excerpt from a datasheet. Refer to Datasheetand other applicable documents for more information.
| Models |
Terminals |
Contact form |
Coil rated voltage |
Model |
| Coil terminals |
Contact terminals |
| Switching / current conduction models |
Screw terminals (See note 2.) |
Screw terminals
(See note 1.) |
SPST-NO |
12 VDC
24 VDC
48 VDC
60 VDC
100 VDC |
G9EC-1-B |
| Lead wire |
G9EC-1 |
| Note:1. |
Two M8 nuts are provided for the contact terminal connection. |
| 2. |
Two M3.5 screws are provided for the coil terminal connection. |
Ratings
Coil
| Rated voltage |
Rated current |
Coil resistance |
Must-operate voltage |
Must-release voltage |
Maximum voltage (See note 3.) |
Power consumption |
| 12 VDC |
938 mA |
12.8 Ω |
75% max. of rated voltage |
8% min. of rated voltage |
110% of rated voltage
(at 23ºC within 10 mimutes) |
Approx. 11 W |
| 24 VDC |
469 mA |
51.2 Ω |
| 48 VDC |
234 mA |
204.8 Ω |
| 60 VDC |
188 mA |
320.0 Ω |
| 100 VDC |
113 mA |
888.9 Ω |
| Note:1. |
The figures for the rated current and coil resistance are for a coil temperature of 23ºC and have a tolerance of ±10%. |
| 2. |
The figures for the operating characteristics are for a coil temperature of 23ºC. |
| 3. |
The figure for the maximum voltage is the maximum voltage that can be applied to the relay coil. |
Contacts
| Item |
Resistive load |
| G9EC-1(-B) |
| Rated load |
200 A at 400 VDC |
| Rated carry current |
200 A |
| Maximum switching voltage |
400 V |
| Maximum switching current |
200 A |
Characteristics
| Item |
G9EC-1(-B) |
| Contact resistance (See note 2.) |
30 mΩ max. (0.2 mΩ typical) |
| Contact voltage drop |
0.1 V max. (for a carry current of 200 A) |
| Operate time |
50 ms max. |
| Release time |
30 ms max. |
Insulation resistance
(See note 3.) |
Between coil and contacts |
1,000 MΩ min. |
| Between contacts of the same polarity |
1,000 MΩ min. |
| Dielectric strength |
Between coil and contacts |
2,500 VAC, 1 min |
| Between contacts of the same polarity |
2,500 VAC, 1 min |
| Impulse withstand voltage (See note 4.) |
4,500 V |
| Vibration resistance |
Destruction |
10 to 55 to 10 Hz, 0.75-mm single amplitude
(Acceleration: 2.94 to 88.9 m/s2) |
| Malfunction |
10 to 55 to 10 Hz, 0.75-mm single amplitude
(Acceleration: 2.94 to 88.9 m/s2) |
| Shock resistance |
Destruction |
490 m/s2 |
| Malfunction |
196m/s2 |
| Mechanical endurance (See note 5.) |
200,000 operations min. |
| Electrical endurance (resistive load) (See note 6.) |
400 VDC, 200 A, 3,000 operations min. |
| Short-time carry current |
300 A (15 min) |
| Maximum interruption current |
1,000 A at 400 VDC (10 times) |
| Overload interruption |
700 A at 400 VDC (40 times min.) |
| Reverse polarity interruption |
-200 A at 200 VDC
(1,000 times min.) |
| Ambient operating temperature |
-40 to 50ºC
(with no icing or condensation) |
| Ambient operating humidity |
5% to 85% |
| Weight |
Approx. 560 g |
| Note:1. |
The above values are initial values at an ambient temperature of 23ºC unless otherwise specified. |
| 2. |
The contact resistance was measured with 1 A at 5 VDC using the voltage drop method. |
| 3. |
The insulation resistance was measured with a 500-VDC megohmmeter. |
| 4. |
The impulse withstand voltage was measured with a JEC-212 (1981) standard impulse voltage waveform (1.2 × 50 μs). |
| 5. |
The mechanical endurance was measured at a switching frequency of 3,600 operations/hr. |
| 6. |
The electrical endurance was measured at a switching frequency of 60 operations/hr. |
Note: All units are in millimeters unless otherwise indicated.
Screw Terminal Type
G9EC-1-B
Mounting Hole Dimensions
(TOP VIEW)

|
Terminal Arrangement /
Internal Connections
(TOP VIEW)

| Note: |
Be sure to connect terminals with the correct polarity. Coils do not have polarity. |
|
| Dimension (mm) |
Tolerance (mm) |
| 10 or lower |
±0.3 |
| 10 to 50 |
±0.5 |
| 50 or higher |
±1 |
|
Models with Lead Wires
G9EC-1
 |
Mounting Hole Dimensions
(TOP VIEW)
 |
Terminal Arrangement /
Internal Connections
(TOP VIEW)

| Note: |
Be sure to connect terminals with the correct polarity. Coils do not have polarity. |
|
|
| Dimension (mm) |
Tolerance (mm) |
| 10 or lower |
±0.3 |
| 10 to 50 |
±0.5 |
| 50 or higher |
±1 |
|
Options
Terminal Cover
P9EC-C

Note:Be sure to remove the cutouts for wiring that are located in the wiring outlet direction before installing the Terminal Cover.
|
| Dimension (mm) |
Tolerance (mm) |
| 10 or lower |
±0.3 |
| 10 to 50 |
±0.5 |
| 50 or higher |
±1 |
|
|
Relays
Product Lineup
Support
Related Links


|